This part of this European Prestandard specifies a test method for determining the ability of a vertical
protective membrane, when used as a fire resistant barrier, to contribute to the fire resistance of loadbearing
vertical structural building members fabricated from steel, concrete, steel / concrete composites or timber.
The method described is applicable to any type of vertical protective membrane, which can be associated
with a separate bracing membrane.
The vertical protective membrane can be separate from the structural building member and be selfsupporting
or can be attached to the structural building member and can form part of any load bearing
structure. This test method is applicable to vertical protective membranes where there is a separating gap
of at least 5 mm size between the vertical protective membrane and the structural building member,
otherwise alternative test methods ENV 13381-3, ENV 13381-4, ENV 13381-6 or ENV 13381-7 should
be used as appropriate
This test method and assessment is not applicable to the following:
a) all situations where the cavity behind the vertical protective membrane contains more than a
specified amount of combustible materials, e.g. electrical cables and pipes, other than where
timber structural members themselves are required;
b) all situations where the cavity is to be used as a service or ventilation shaft;
c) all situations where the vertical protective membrane acts as a bracing membrane.
This European Prestandard contains the fire test which specifies the tests which should be carried out
whereby the vertical protective membrane together with the structural member to be protected is exposed
to the specified fire. The fire exposure, to the standard temperature/time curve given in EN 1363-1, is
applied to the side which would be exposed in practice.
The test method makes provision, through specified optional additional procedures, for the collection of
data which can be used as direct input to the calculation of fire resistance according to the processes given
in ENV 1992-1-2, ENV 1993-1-2, ENV 1994-1-2 and ENV 1995-1-2.
This European Prestandard also contains the assessment which provides information relative to the analysis
of the test data and gives guidance for the interpretation of the results of the fire test, in terms of
loadbearing capacity criteria of the protected vertical structural member.
The results of the fire test and the assessment can be applied, with certain defined provisions, to vertical
structural building members which can be beams, columns or a combination of both and / or which could
form part of a separating element or partition.
The limits of applicability of the results of the assessment arising from the fire test are defined, together
with permitted direct application of the results to different structures, membranes and fittings.