This CSA Standard is a bi-national Standard with UL 5085-3. 1 Scope 1.1
As noted in Low Voltage Transformers - Part 1: General Requirements, UL 5085-1, or CSA C22.2 No. 66.1, Low Voltage Transformers - Part 1: General Requirements, the requirements in Part 3 cover Class 2 transformers for use with Class 2 circuits in accordance with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, Part I, CSA C22.1.
They are intended for connection to essentially sinusoidal supply sources. Advisory Note: For transformers intended for use in the United States, these requirements also cover Class 3 transformers for use with Class 3 circuits in accordance with the National Electrical Code, ANSI/NFPA 70, unless otherwise specified in this standard. See Annex D for Class 3 requirements. 1.3
In addition to the items specified in Clause 1.3 of Part 1, the requirements of Part 3 do not cover:
a) Power supplies (a transformer provided with a rectifier is considered a power supply);
b) Toy transformers;
c) Cord and plug connected transformers;
d) Direct plug-in transformers;
e) Transformers intended for use in audio, radio, or television type appliances; or
f) Other special types of transformers covered in requirements for other electrical devices or appliances. Advisory Note: The requirements of Part 3 do not cover transformers intended for use in the United States having a nominal primary rating of more than 600 V and transformers having overvoltage taps rated over 660 V. 1.7
This part is intended to be used in conjunction with Part 1. The numbering of the clauses in Part 3 corresponds to the numbered clauses in Part 1. The requirements in Part 1 apply unless modified by Part 3. 1.8
A Class 2 transformer that includes a separate current-limiting impedance such as a resistor or a positive temperature coefficient device (PTC) is covered by these requirements. 1.9
A Class 2 transformer that includes a resonance regulating circuit is covered by these requirements.