UL 360-2003
防液渗的柔性钢导管

Liquid-tight flexible steel conduit


说明:

  • 此图仅显示与当前标准最近的5级引用;
  • 鼠标放置在图上可以看到标题编号;
  • 此图可以通过鼠标滚轮放大或者缩小;
  • 表示标准的节点,可以拖动;
  • 绿色表示标准:UL 360-2003 , 绿色、红色表示本平台存在此标准,您可以下载或者购买,灰色表示平台不存在此标准;
  • 箭头终点方向的标准引用了起点方向的标准。

 

 

非常抱歉,我们暂时无法提供预览,您可以试试: 免费下载 UL 360-2003 前三页,或者稍后再访问。

点击下载后,生成下载文件时间比较长,请耐心等待......

 



标准号
UL 360-2003
发布日期
2003年06月25日
实施日期
废止日期
中国标准分类号
H48
国际标准分类号
29.120.10
发布单位
US-UL
代替标准
UL 360-2009
适用范围
1.1 These requirements cover the 3/8 (12), 1/2 (16), 3/4 (21), 1 (27), 1-1/4 (35), 1-1/2 (41), 2 (53), 2-1/2(63), 3 (78), 3–1/2 (91), and 4 (103) trade sizes (metric designators) of liquid-tight flexible steel conduit. The conduit covered is intended for installation in accordance with the National Electrical Code (NFPA 70)as raceway for wires and cables in motor circuits operating at potentials over 600 volts, in electric-sign circuits operating at potentials up through 1000 volts, over 1000 volts, and in other circuits operating at 0–600 V. 1.2 This conduit is for applications in which flexibility of the conduit is necessary during installation, operation, or maintenance and the contained conductors need protection from vapors, liquids or solids. 1.3 This conduit is circular in cross section, having an outer liquid-tight, nonmetallic, sunlight-resistant jacket over an inner flexible metal core, and is for use in wet, dry, or oily locations in which the conduit is exposed but is not subject to physical damage. Conduit that is not marked with a temperature designation or is marked "60 C" is for use at temperatures not in excess of 60°C (140°F). Conduit that is for use in dry or oily locations at a temperature higher than 60°C (140°F) is marked "____C dry, 60 C wet, 70 C oil res" or "____C dry, 60 C wet, 70 C oil resistant" with "80 C" or "105 C"inserted as the dry-locations temperature. 1.4 Conduit that is marked "80 C dry, 60 C wet, 60 C oil res" or "80 C dry, 60 C wet, 60 C oil resistant" is for use at 80°C (176°F) and lower temperatures in air, and 60 °C (140°F) and lower temperatures where exposed to water, oil or coolants - that is, to cutting oils and the like in machine - tool and other industrial applications. 1.5 Conduit marked in accordance with 23.4(g) is limited to use in oil free environments. 1.6 Fittings for liquid-tight flexible steel conduit are covered in the Standard for Fittings for Cable and Conduit, UL 514B. 1.7 These requirements do not cover liquid-tight flexible nonmetallic conduit. Flexible nonmetallic conduit is covered in the Standard for Liquid-Tight Flexible Nonmetallic Conduit, UL 1660, and the fittings for this conduit are covered in the Standard for Fittings for Cable and Conduit, UL 514B. 1.8 These requirements do not cover flexible metallic tubing. 1.9 These requirements do not cover electrical nonmetallic tubing (ENT).




Copyright ©2007-2022 ANTPEDIA, All Rights Reserved
京ICP备07018254号 京公网安备1101085018 电信与信息服务业务经营许可证:京ICP证110310号