Standard Practice for Joint Acceptance Testing of Installed Precast Concrete Pipe Sewer Lines


ASTM C1103-2003 发布历史

This is not a routine test. The values recorded are applicable only to the sewer being tested and at the time of testing.

1.1 This practice covers procedures for testing the joints of installed precast concrete pipe sewer lines, when using either air or water under low pressure to demonstrate the integrity of the joint and the construction procedures. This practice is used for testing 27-in. and larger diameter precast concrete sewer lines utilizing rubber gasket sealed joints.

1.2 A complete metric companion to Practice C 1103 has been developed-C 1103M; therefore, no metric equivalents are presented in this practice.

Note 18212;The owner shall specify the following: who will conduct, observe, and furnish labor, material, and measuring devices and pay for the tests; who is responsible for determining local ground conditions; and whether an air or water test is to be used.

Note 28212;The user of this practice is advised that test criteria presented in this practice are similar to those in general use. Pipe 24-in. diameter and smaller shall be accepted by infiltration or exfiltration testing utilizing Practice C 969 or by low pressure air testing utilizing Practice C 924. Pipe greater than 24-in. diameter shall be accepted by infiltration or exfiltration testing utilizing C 969.

Note 38212;The user of this practice is advised that no correlation has been found between air loss and water leakage.

1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. Specific precautions are given in Section 6.

ASTM C1103-2003由美国材料与试验协会 US-ASTM 发布于 2003。

ASTM C1103-2003 在中国标准分类中归属于: Q14 混凝土制品。

ASTM C1103-2003的历代版本如下:

  • 2002年08月10日 ASTM C1103-02 已安装的预制混凝土污水管接头验收试验的标准实施规程
  • 2003年11月01日 ASTM C1103-03 已安装的预制混凝土污水管接头验收试验的标准实施规程
  • 2009年06月01日 ASTM C1103-03(2009) 已安装的预制混凝土污水管接头验收试验的标准实施规程
  • 2014年11月15日 ASTM C1103-14 已安装的预制混凝土污水管接头验收试验的标准实施规程
  • 2019年01月01日 ASTM C1103-19 已安装的预制混凝土污水管接头验收试验的标准实施规程
  • 1994年 ASTM C1103-1994(2000)
  • 2002年 ASTM C1103-2002 安装完毕的预制混凝土污水管线接头的验收校验标准实施规程
  • 2003年 ASTM C1103-2003 已安装的预制混凝土污水管线的接头验收试验的标准规程
  • 2003年 ASTM C1103-2003(2009) 已安装的预制混凝土污水管线的接头验收试验的标准实施规程
  • 2014年 ASTM C1103-2014 已安装的预制混凝土污水管线接头验收试验的标准实践规程
  • 2000年01月01日 ASTM C1103-94(2000) 已安装的预制混凝土污水管接头验收试验的标准实施规程

 

 

非常抱歉,我们暂时无法提供预览,您可以试试: 免费下载 ASTM C1103-2003 前三页,或者稍后再访问。

点击下载后,生成下载文件时间比较长,请耐心等待......

 



标准号
ASTM C1103-2003
发布日期
2003年
实施日期
废止日期
中国标准分类号
Q14
国际标准分类号
23.040.50 (Pipes and fittings of other materials)
发布单位
US-ASTM
适用范围

This is not a routine test. The values recorded are applicable only to the sewer being tested and at the time of testing.

1.1 This practice covers procedures for testing the joints of installed precast concrete pipe sewer lines, when using either air or water under low pressure to demonstrate the integrity of the joint and the construction procedures. This practice is used for testing 27-in. and larger diameter precast concrete sewer lines utilizing rubber gasket sealed joints.

1.2 A complete metric companion to Practice C 1103 has been developed-C 1103M; therefore, no metric equivalents are presented in this practice.

Note 18212;The owner shall specify the following: who will conduct, observe, and furnish labor, material, and measuring devices and pay for the tests; who is responsible for determining local ground conditions; and whether an air or water test is to be used.

Note 28212;The user of this practice is advised that test criteria presented in this practice are similar to those in general use. Pipe 24-in. diameter and smaller shall be accepted by infiltration or exfiltration testing utilizing Practice C 969 or by low pressure air testing utilizing Practice C 924. Pipe greater than 24-in. diameter shall be accepted by infiltration or exfiltration testing utilizing C 969.

Note 38212;The user of this practice is advised that no correlation has been found between air loss and water leakage.

1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. Specific precautions are given in Section 6.