UL 60947-7-2-2004 低压开关设备和控制设备.第7-2部分:辅助设备.铜导线用保护导线接线端子排
UL Standard for Safety Low-Voltage Switchgear and Controlgear Part 7-2: Ancillary Equipment Protective Conductor Terminal Blocks for Copper Conductors Second Edition
1.1 This part of IEC 60947 specifies requirements for protective conductor terminal blocks with PE function up to 120 mm2 (250 kcmil) and for protective conductor terminal blocks with PEN function equal to and above 10 mm2 (AWG 8) with screw-type or screwless-type clamping units, primarily intended for industrial applications. NOTE: AWG is the abbreviation of "American Wire Gage" [Gage (US) = Gauge (UK)] kcmil = 1000 cmil1 cmil = 1 circular mil = surface of a circle having a diameter of 1 mil 1 mil = 1/1000 inch. Protective conductor terminal blocks are used to form the electrical and mechanical connection between copper conductors and the fixing support. lt is applicable to protective conductor terminal blocks for the connection of round copper conductors with or without special preparation having a cross-section between 0,2 mm2 and 120 mm2 (AWG 24 and 250 kcmil), intended to be used in circuits of a rated voltage not exceeding 1000 V a.c. up to 1000 Hz or 1500 V d.c., most commonly in conjunction with terminal blocks according to IEC 60947-7-1. 1.1 Addition: AWG range expanded to include AWG 30. 1.1 Addition: This standard applies to insulation displacement terminals. 1.1 Addition: PEN does not apply. This standard may be used as guide for - protective conductor terminal blocks requiring the fixing of special devices to the conductors, for example quick connect terminations or wrapped connections, etc.; - protective conductor terminal blocks providing direct contact to the conductors by means of edges or points penetrating the insulation, for example insulation displacement connections, etc. Where applicable in this standard, the term "clamping unit" has been used instead of the term "terminal". This is taken into account in case of reference to IEC 60947-1.