ASTM E2923-13
使用差示扫描量热法评估挡火材料寿命的标准实施规程

Standard Practice for Longevity Assessment of Firestop Materials Using Differential Scanning Calorimetry


 

 

非常抱歉,我们暂时无法提供预览,您可以试试: 免费下载 ASTM E2923-13 前三页,或者稍后再访问。

您也可以尝试购买此标准,
点击右侧 “购买” 按钮开始采购(由第三方提供)。

点击下载后,生成下载文件时间比较长,请耐心等待......

 

标准号
ASTM E2923-13
发布
2013年
发布单位
美国材料与试验协会
替代标准
ASTM E2923-14
当前最新
ASTM E2923-14(2019)
 
 
适用范围

5.1 Firestop systems are exposed to fire tests and classified using materials that have been, in all likelihood, quite recently manufactured. The testing provides a fire resistance rating for the firestop system that is measured in hours. The goal of firestop system testing is to identify and list firestop systems that will have a fire resistance rating that is no less than the fire resistance rating of the classified wall or floor assembly in which it is installed. A building fire that could put the firestop system to the test can occur at any time during the life of the building. By that time, the firestop system is composed of materials that have aged. Some assurance is desired to establish quantitatively that the firestop system will continue to have a fire resistance rating that is no less than that of the wall or floor assembly.

5.2 This practice provides one method for examining whether any changes are to be expected in the characteristics of a firestop material during its design life, as gauged by any chemical reactions that occur within the material to change it. The measurement of conversion rate provides a standard measure of how much a material will change over its design life. This provides an objective indication of whether the bulk of the material is likely to exhibit the desirable properties for which it was chosen in the firestop system.

5.3 Measurement of conversion rate allows different firestop materials used for similar purposes to be compared with respect to their ability to remain unchanged during their design life.

5.3.1 This allows materials with an unusually high conversion rate to be questioned and possibly rejected early on during the research and development process.

5.3.2 This allows materials to be screened by testing and listing agencies to ensure that they do not provide a listing for products that are not likely to have adequate performance for the full length of the intended design life.

5.3.3 This allows formulation changes that have no apparent impact on the results of the fire testing to be evaluated for any possible long-term consequences on performance.

5.3.4 Re-calculation of the conversion rate (other than for the standard time and temperature specified in Section 11) allows materials to be evaluated for suitability in applications where they may be regularly exposed to unusually high temperatures, or for suitability in installations which are intended to have an unusually long design life, or both.

5.4 Measurement of conversion rate allows longevity of firestop materials to be compared to the longevity of the classified wall or floor assemblies in which the firestop system is installed, by measuring the conversion rate for each. This comparison can ensure that the firestop system does not degrade significantly faster, thus possibly deeming it to be unacceptable. The comparison can also ensure that the firestop system is not unjustifiably held to a higher standard of longevity than the floor or wall itself.

5.5 The fundamental assumption inherent in making use of DSC conversion rate data for assessing longevity of firestop materials is that if the material has a che......