Introducing Using the Heat Wheel to Cool the Computer Room


 

 

非常抱歉,我们暂时无法提供预览,您可以试试: 免费下载 LO-09-014-2009 前三页,或者稍后再访问。

如果您需要购买此标准的全文,请联系:

点击下载后,生成下载文件时间比较长,请耐心等待......

 

标准号
LO-09-014-2009
发布日期
2009年01月01日
实施日期
2010年02月10日
废止日期
中国标准分类号
/
国际标准分类号
/
发布单位
ASHRAE - American Society of Heating@ Refrigerating and Air-Conditioning Engineers@ Inc.
引用标准
5
适用范围
"ABSTRACT There is a growing trend to utilize economical ways to cool data centers@ which includes maximizing the use of ""free cooling"" techniques such as airside and waterside economizing. A new economizer cooling system is being developed and tested at this time and will be implemented in a number of data centers within the next year. This technique uses a heat wheel to transfer the heat from the computer room to the ambient environment with a minimal transfer of air and moisture. It has been shown to have the capability of cooling a computer room with a heat density of 600 W/ft? and a cabinet heat load of 70 kW. It can provide cooling throughout the computer room within the existing ASHRAE guidelines up to an ambient condition of 22??(72??. It has been demonstrated to handle a temperature rise through cabinets of over 28??(50??. It can accomplish all this with a mechanical efficiency as low as 0.03@ which for 550 kW load in the computer room only 17 kW of mechanical energy was being utilized."